SEEKU WSFE-485-056 RS485 LED Display – Wiring, Modbus RTU, PC Setup & Troubleshooting

AUSCOMTECH PRODUCT SUPPORT

SEEKU WSFE-485-056 RS485 LED Display – Wiring, Modbus RTU, PC Setup & Troubleshooting

Model: SEEKU WSFE-485-056

The SEEKU WSFE-485-056 is a compact industrial four-digit LED display designed to show numerical values, decimal numbers and supported text characters received from a PLC, computer or other RS485 controller.

It features a red 0.56-inch LED display, a 7–36V DC power input and an RS485 communication interface supporting Modbus RTU and ASCII display commands.

This guide covers wiring, PLC connections, PC testing with a USB-to-RS485 converter, the Modbus register map, hexadecimal command examples, signed numbers, decimal points, display brightness, communication settings and troubleshooting.

SEEKU WSFE-485-056 Overview

The WSFE-485-056 is a remote numerical indicator. It receives display information through its RS485 interface and controls the LED segments internally.

It does not independently measure temperature, voltage or current. The connected controller must acquire or calculate the required value and transmit the corresponding display command.

Manufacturer / Model SEEKU WSFE-485-056
Display 4 × 0.56″ Red LED
Power Supply 7–36V DC
Communication 2-Wire RS485
Protocols Modbus RTU / ASCII
Current Consumption Approx. 30mA

Technical Specifications

ParameterSpecification
ModelWSFE-485-056
Display type4-digit, 7-segment LED
Digit size0.56 inch (approximately 14.2mm)
Display colourRed
Power input7–36V DC
Typical currentApproximately 30mA
CommunicationRS485, 2-wire half-duplex
IsolationNon-isolated RS485 interface
ProtocolsModbus RTU and ASCII display commands
Supported baud rates1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200bps
Overall dimensions79 × 43 × 21.5mm
Panel cut-out76 × 39.2mm

Power & RS485 Connections

The display requires a DC power connection and a separate RS485 communication connection.

Display TerminalFunctionConnection
V+ / Power +Positive DC supplyExternal 7–36V DC positive
GND / Power −DC negative and signal referenceExternal DC negative
A / 485ARS485 differential data AController or converter A
B / 485BRS485 differential data BController or converter B
Provide a separate DC supply.

The RS485 interface does not power the display. Use a suitable regulated 12V or 24V DC supply for normal testing and installation.

Never connect the DC power positive terminal to RS485 A, RS485 B or a USB converter terminal. Disconnect power before changing wiring.

Non-Isolated RS485

The WSFE-485-056 uses a non-isolated RS485 interface. Its communication circuitry shares an electrical reference with its power supply.

For non-isolated installations, the RS485 devices must remain within their permitted common-mode voltage range. A suitable common signal reference or galvanically isolated interface may be required.

Industrial grounding

Do not assume equipment in separate cabinets or powered from unrelated supplies has compatible ground potentials. Use appropriately isolated RS485 equipment where significant ground differences or electrical transients may occur.

Connecting the Display to a PLC

A PLC with a compatible RS485 port and Modbus RTU master capability can control the display directly.

SEEKU DisplayPLC / Supply
V+External 12V or 24V DC positive
GNDExternal DC negative
485APLC RS485 A
485BPLC RS485 B
Signal referenceSuitable common reference or isolation arrangement

PLC Configuration

  1. Connect the display to its regulated DC supply.
  2. Connect the PLC RS485 A and B signals.
  3. Configure the PLC as a Modbus RTU master.
  4. Set the serial speed and frame format to match the display.
  5. Enter the configured slave address. The manual gives address 1 as the default.
  6. Use the required Modbus function and register from the register map below.
  7. Send a test value and check the LED display.
Register addressing in PLC software

The hexadecimal addresses in this guide are Modbus protocol addresses. Some PLC packages use conventional holding-register numbers beginning at 40001, while others use zero-based addresses.

For example, protocol address 0x0000 may appear as holding register 40001 in a one-based numbering system. Check the addressing convention used by your PLC software.

PC Connection with a USB-to-RS485 Converter

A USB-to-RS485 converter provides a convenient way to test the display from a Windows computer without a PLC.

Optional accessory: AuscomTech USB-to-RS485 Converter

AuscomTech supplies a CH340 USB-to-RS485 converter with a 2-wire half-duplex interface, A/B screw terminals and Power, TX and RX indicators.

View the AuscomTech USB-to-RS485 CH340 Converter

USB Converter Wiring

ConnectionDestination
Converter ADisplay 485A
Converter BDisplay 485B
External 12V positiveDisplay V+
External 12V negativeDisplay GND
USB connectorComputer USB port
Two-terminal adapter limitation

The AuscomTech converter has two external RS485 terminals, A and B, but no separate signal-ground terminal. The display's interface is non-isolated.

Use this arrangement only where the RS485 common-mode voltage is within permitted limits. For a defined signal-reference connection or electrically separated industrial equipment, use a converter with suitable grounding provision or galvanic isolation.

Installing the CH340 Driver

  1. Connect the converter to the computer USB port.
  2. Open Windows Device Manager.
  3. Expand Ports (COM & LPT).
  4. Locate the USB serial converter and note its COM port number.
  5. If Windows does not recognise the converter, install an appropriate CH340/CH341 driver from a trusted manufacturer source.
  6. Reconnect the adapter and confirm that the COM port is available.

Complete Modbus Register Reference

The following table covers the Modbus registers documented in the supplied communication manual, including normal numerical display operation, persistent communication settings, brightness, flashing and advanced display functions.

Addresses are hexadecimal protocol addresses. Function 06 writes one holding register; function 10 hexadecimal (decimal 16) writes multiple holding registers.

Register Function Modbus Function Data / Range Persistence
0x0000 Display integer value 06 16-bit integer display data Display state; default has no decimal point
0x0002 RS485 slave address 06 1–254 (0x01–0xFE) Saved
0x0003 Baud rate 06 Codes 0–7 Saved
0x0004 Decimal-point position 06 0–3 Lost after power-off
0x0005 Brightness 06 0–7 Saved
0x0006 Flashing / flicker 06 0–7 documented; 0 = off, 1 = on Lost after power-off
0x0070 ASCII character display 10 hex 6 registers / 12 ASCII bytes Display data
0x0090 Signed numerical value with decimal point 10 hex 2 registers / 4 data bytes Display data
Important register distinction

Register 0x0090 is the signed-number display register and 0x0070 is the ASCII character display register. They are not registers 0x0009 and 0x0007.

Both advanced functions use Modbus function 0x10, Write Multiple Registers.

Modbus RTU – Hexadecimal Command Examples

All commands in this section use slave address 01. The last two bytes are the Modbus RTU CRC-16, transmitted low byte first.

The commands must be sent as raw hexadecimal bytes, not as ordinary ASCII text.

1. Display Integer 8888

Write decimal 8888 (hexadecimal 0x22B8) to register 0x0000.

Display 8888 – Function 06
01 06 00 00 22 B8 91 18

Expected result: The LED display shows 8888.

2. Display Integer 1234

The following example writes decimal 1234 (hexadecimal 0x04D2) using the same register. Its CRC has been calculated for this value.

Display 1234 – Function 06
01 06 00 00 04 D2 0B 57

Expected result: The LED display shows 1234.

3. Set One Decimal Place

Register 0x0004 sets the number of digits after the decimal point. The value 1 selects one decimal place.

Set One Decimal Place – Function 06
01 06 00 04 00 01 09 CB

For example, if the displayed integer is 324, one decimal place represents 32.4.

Register ValueDecimal PlacesExample for 1234
0None1234
1One123.4
2Two12.34
3Three1.234
Decimal-point setting is temporary.

The manual states that register 0x0004 loses its setting after a power interruption. The default is no decimal point. The controller should resend the required decimal-point setting after the display powers up.

4. Change Slave Address to 2

Register 0x0002 controls the RS485 station address. This example changes the address from 1 to 2.

Set Slave Address 2 – Function 06
01 06 00 02 00 02 A9 CB

Expected result: The display accepts the address-change command. Future commands must use slave address 02.

Configuration write – use with care.

This changes a saved setting. Do not send it during normal display-value testing. After changing the address, subsequent commands addressed to 01 may no longer communicate with the display.

The manual documents address values from 0x01 to 0xFE and gives 0x01 as the default.

5. Configure 9600 Baud

Register 0x0003 sets the serial baud rate using a numeric code. The code for 9600bps is 3.

Set 9600 Baud – Function 06
01 06 00 03 00 03 39 CB

This command assumes the display's current address is 1. Transmit it at the display's current baud rate, then configure the controller to communicate at 9600bps after the setting takes effect.

Baud Rate Register Codes

Register ValueBaud Rate
01200bps
12400bps
24800bps
39600bps
419200bps
538400bps
657600bps
7115200bps

The manual states that the baud-rate parameter is saved permanently and gives code 3 (9600bps) as the default.

6. Set Maximum Brightness

Register 0x0005 controls brightness. Valid values are 0–7, where 0 is darkest and 7 is brightest.

Set Brightness to 7 – Function 06
01 06 00 05 00 07 D8 09

Expected result: The display changes to brightness level 7. The manual identifies this as the default and states that the setting is retained after power-off.

7. Enable Display Flashing

Register 0x0006 controls the display flashing function.

Enable Flashing – Function 06
01 06 00 06 00 01 A8 0B

Expected result: The display flashes.

The manual identifies value 0 as flashing disabled and value 1 as flashing enabled. It also lists a value range of 0–7, but does not clearly define all intermediate behaviours. Use 0 and 1 for basic on/off control.

The flashing setting is temporary and defaults to off after power is removed.

Advanced Modbus Display Functions

Besides ordinary integer display, the module supports signed numerical values, decimal positions and ASCII character display using Modbus function 0x10.

Register 0x0090 – Signed Number with Decimal Point

This operation writes two consecutive holding registers starting at address 0x0090. The data payload contains four bytes:

Byte PositionFunction
Byte 1Sign: 0 = positive, 1 = negative
Byte 2Decimal places: 0, 1 or 2
Bytes 3–416-bit numerical value, high byte first

The numerical value is interpreted using the selected decimal-place setting. For example, raw decimal 490 with two decimal places represents 4.90.

Example – Display 4.90

Display 4.90 – Function 10 Hex
01 10 00 90 00 02 04 00 02 01 EA DB 1C

Command breakdown:

BytesMeaning
01Slave address 1
10Write Multiple Registers
00 90Starting register 0x0090
00 02Write two registers
04Four data bytes
00Positive number
02Two decimal places
01 EADecimal 490
DB 1CCRC-16

Expected result: The LED displays 4.90.

Example – Display -1.0

Display -1.0 – Function 10 Hex
01 10 00 90 00 02 04 01 01 00 0A 2A F8

Here, the first data byte selects a negative number, the second data byte selects one decimal place and the numerical data represents 10.

Expected result: The display shows -1.0.

Example – Display 0.2

Display 0.2 – Function 10 Hex
01 10 00 90 00 02 04 00 01 00 02 2A C2

Expected result: The display shows 0.2.

Multi-register writes in PLC software

Select Modbus function 16 decimal (0x10 hexadecimal), starting register address 0x0090, with two registers and four bytes of data.

Do not use function 06 for this operation. The signed-number format requires the complete four-byte payload.

Register 0x0070 – Display ASCII Characters

The ASCII-character display function uses Modbus RTU function 0x10 to write six consecutive holding registers starting at address 0x0070.

The payload contains 12 bytes of ASCII character data. The manual shows text beginning at the left side of the display, with excess character positions filled using zero bytes.

Example – Display P2.3

Display P2.3 – Function 10 Hex
01 10 00 70 00 06 0C
50 32 2E 33 00 00 00 00 00 00 00 00
3B 25

Data interpretation:

ASCII HexCharacter
50P
322
2EDecimal point (.)
333
00Unused / padding positions

Expected result: The display shows P2.3 using the available seven-segment character representations.

ASCII characters are still being sent inside a Modbus RTU frame.

This is different from the separate ASCII communication protocol. The ASCII character-display operation uses Modbus function 0x10, register 0x0070 and a binary Modbus RTU frame with CRC.

The seven-segment display cannot reproduce every alphabetic character exactly as it appears on a computer screen.

Separate ASCII Communication Protocol

In addition to Modbus RTU, the communication manual describes a manufacturer-specific ASCII command protocol.

This protocol uses printable characters to communicate with the display. It is distinct from the Modbus RTU multi-register ASCII-character operation described above.

Basic ASCII Display Command

The manual provides an address-prefixed display command using dollar-sign and hash-sign framing.

ASCII – Display 1234
$001,1234#

In this command:

PartMeaning
$Command start
001Display address 1
,Address/data separator
1234Display content
#Command terminator

Expected result: The display shows 1234 when configured to recognise this ASCII command format and address.

ASCII Display Capabilities

The manual describes commands for display data, address modification, brightness adjustment, software-version information and control/status queries.

Because these commands can affect stored configuration, use the exact syntax specified for the relevant operation. Avoid sending guessed command variations.

ASCII and Modbus RTU are different message formats.

For a Modbus RTU command, send raw binary bytes with the correct CRC. For the manufacturer's ASCII display command, send the literal printable command characters.

A text terminal cannot generate a Modbus RTU frame simply by typing hexadecimal characters separated by spaces.

Practical PC Test – USB-to-RS485

The easiest way to check display operation without a PLC is to use a suitable USB-to-RS485 converter and a Modbus RTU master application.

Step 1 – Connect the Hardware

  1. Disconnect power while connecting the display.
  2. Connect the USB converter A and B terminals to the corresponding display terminals.
  3. Connect the display to its external regulated DC supply.
  4. Ensure the installation has a suitable RS485 electrical reference.
  5. Connect the USB converter to the computer.

Step 2 – Configure the Serial Connection

Use a Modbus RTU master application such as QModMaster or other suitable industrial Modbus testing software.

ParameterInitial Setting
ModeModbus RTU
Serial portConverter COM port
Slave address1 (manual default)
Baud rate9600bps (manual default)
Data bits8
ParityNone
Stop bits1

If the display has previously been configured, use its current stored settings instead.

Step 3 – Write a Test Display Value

  1. Select slave address 1.
  2. Select function 06, Write Single Holding Register.
  3. Enter register address 0x0000 using the addressing convention of the software.
  4. Enter decimal value 1234.
  5. Send the command.
  6. Observe the LED display.

Expected Result

The display should show 1234. If the application reports a response, confirm the response is valid and that the display has actually changed.

As a second test, write decimal 8888 to the same register. The display should update to 8888.

Testing with Raw Hexadecimal Software

Some serial diagnostic applications allow raw hexadecimal transmission rather than a conventional Modbus register interface.

For display 8888, transmit:

Raw RTU Frame – Display 8888
01 06 00 00 22 B8 91 18

Ensure the application is set to transmit hexadecimal bytes, not the literal character string shown above. Do not append carriage-return or line-feed characters to a Modbus RTU frame.

Local Configuration & Communication Settings

The communication manual also describes a local configuration system using two control switches on the rear circuit board.

Configuration Switches

The manual identifies:

  • SW1: Menu / configuration selection
  • SW2: Down / parameter adjustment

The configuration interface allows the operator to navigate through normal display operation, address, baud rate, protocol, brightness and save options.

Follow the switch labels and menu indications on the supplied unit. Do not short unrelated PCB contacts or assume that every hardware revision uses the same switch arrangement.

Reported Menu Sequence

Menu ExampleMeaning
1234Normal numerical display
A001Station address 1
969600 baud display setting
d-0Protocol setting, shown in the manual example
b-7Brightness setting
YESSave configuration

Changing the Station Address

The default address stated in the manual is 1. Address values from 1 to 254 are documented.

  1. Record the current station address.
  2. Enter the local configuration menu using the documented switches.
  3. Navigate to the address parameter.
  4. Select a unique address for the RS485 network.
  5. Confirm and save the parameter as required.
  6. Reconfigure the PLC or PC software for the new address.

Changing the Baud Rate

The manual gives 9600bps as the default and supports the following settings:

Baud RateModbus Register Code
12000
24001
48002
96003
192004
384005
576006
1152007

When the baud rate changes, the controller must also be configured for the new speed.

Brightness Configuration

The Modbus brightness register supports levels 0–7, with 7 as the brightest setting. The manual gives level 7 as the default.

The brightness value is retained after a power interruption.

Temporary Versus Saved Settings

ParameterPower-Cycle Behaviour
Slave addressSaved
Baud rateSaved
BrightnessSaved
Decimal-point settingResets to no decimal point
Flashing settingResets to flashing disabled

For applications requiring a fixed decimal-point position or flashing behaviour, configure the controller to resend those temporary settings after power-up.

Industrial RS485 Installation Notes

Cabling

  • Use suitable twisted-pair cable for RS485 A and B.
  • Prefer daisy-chain wiring over long star-shaped branches.
  • Keep communication wiring away from high-current motor and mains wiring where practical.
  • Provide suitable signal reference or isolation between devices.
  • Keep branch cables short.

Termination

Longer RS485 cable runs commonly require termination at the two physical ends of the bus. A typical termination value is 120 ohms when matched to the cable and transceivers.

Do not fit termination resistors across every connected display. Excess termination can overload the RS485 drivers.

Multiple Displays

Multiple displays can share an RS485 bus when configured with appropriate addressing.

Each independently controlled display should have a unique station address. Ensure the Modbus master addresses the intended device and that only one master drives the bus at a time.

Troubleshooting

Display Does Not Power On

  • Measure the voltage directly at V+ and GND.
  • Confirm the power supply is within 7–36V DC.
  • Check supply polarity.
  • Inspect wiring and terminal connections.
  • Check that the supply has sufficient capacity.

Display Powers Up but Does Not Respond

  • Confirm RS485 A and B wiring.
  • Check that the controller and display use matching baud rates.
  • Verify the slave address.
  • Check the protocol mode.
  • Confirm the transmitted Modbus frame includes a valid CRC.
  • Check the electrical reference and common-mode limits of the RS485 interface.

Modbus Write Does Not Change the Display

  • For ordinary integers, use function 06 and register 0x0000.
  • Check whether the PLC uses zero-based or one-based register numbering.
  • Confirm the transmitted numerical value is correct.
  • Check that the display is addressed correctly.
  • Try the documented 8888 command using a compatible raw hexadecimal tool.
  • Verify that the correct communication protocol is selected.

Signed Numbers or Decimal Points Are Wrong

  • Use register 0x0090 with function 0x10 for the documented signed-number format.
  • Check the sign byte: 0 for positive, 1 for negative.
  • Check the decimal-place byte.
  • Verify the two-byte numerical value is transmitted high byte first.
  • For ordinary unsigned integer display, check register 0x0004 for decimal-point positioning.
  • Remember that the ordinary decimal-point setting resets after power-off.

ASCII Text Does Not Display Correctly

  • For ASCII character display through Modbus RTU, use starting register 0x0070.
  • Select function 0x10, Write Multiple Registers.
  • Send six registers containing 12 data bytes.
  • Check the ASCII character values and unused padding bytes.
  • Remember that seven-segment displays cannot reproduce every letter exactly.
  • Do not confuse this operation with the separate ASCII serial protocol.

Slave Address Changed Unexpectedly

  • Check whether a previous command wrote to register 0x0002.
  • Inspect the current station address using the local configuration interface.
  • Reconnect the Modbus master using the new address.
  • Record the correct address before returning the display to service.

USB-to-RS485 Converter Is Not Detected

  • Check the computer USB port.
  • Inspect Ports (COM & LPT) in Device Manager.
  • Install an appropriate CH340/CH341 driver if required.
  • Confirm no other software is using the COM port.
  • Reconnect the converter and check its assigned COM port.

TX LED Flashes but the Display Does Not Update

  • TX activity shows that data is being transmitted, not that the display accepted it.
  • Check the A/B terminal connections and polarity.
  • Verify the display power supply.
  • Confirm the baud rate, station address and function code.
  • Check the RS485 electrical reference and common-mode requirements.
  • Use a suitable analyser or Modbus diagnostic tool when necessary.

Communication Is Intermittent

  • Check connector tightness and cable continuity.
  • Use suitable twisted-pair cabling.
  • Keep communication wiring away from electrical interference.
  • Check bus termination and biasing.
  • Reduce the baud rate if appropriate.
  • Consider galvanic isolation for electrically noisy or distributed installations.
⚠️ Important

The SEEKU WSFE-485-056 is an industrial LED display requiring a regulated 7–36V DC supply. Its non-isolated RS485 interface must be installed with suitable grounding, electrical protection and isolation where required.

The Modbus registers and hexadecimal commands in this guide are transcribed from the supplied communication manual for this display type. Firmware and hardware revisions may differ. Always check the terminal markings, configured address and communication parameters of the actual unit before performing configuration writes.

Registers 0x0002, 0x0003 and 0x0005 change saved settings. Use these commands only when intentionally configuring the device. Disconnect power before changing wiring and verify operation before returning industrial equipment to service.